| Case Name: | Application Case of Partial Discharge Detection for Electrical Equipment in Power Substations |
| Industry Field: | Power / Transmission and Transformation Maintenance |
| Detection Objects: | Substation equipment, switch cabinets, busbar connection points, insulators, transmission cables |
| Use the equipment | 72-channel acoustic imager (model: AC-D100) |
| 128-channel acoustic imager(model: AC-D128PD) | |
| Detection time: | 2024 |
| Detection locations: | Yunnan, Beijing, electricity, Dongguan |
| Guangzhou, Foshan, Jiangsu, Nanchang |
Application background
(1) Field background
During the long-term operation of power transmission and transformation equipment, due to insulation aging,
manufacturing defects, installation process changes,or changes in the operating environment,
local discharge phenomena may occur inside or on the surface of the electrical equipment.
Local discharge is an important early signal of insulation deterioration. If not detected in time,
it may further develop into insulation breakdown, equipment failure, or even power outage accidents.
(2) Core customer requirements
① Conduct non-contact, long-distance detection of local discharge while the equipment is energized,
and determine the type of local discharge.
② Early detection of early and concealed local discharge hazards.
③ Implement daily inspection and status assessment of key equipment.
④ Provide intuitive, recordable, and comparable detection results.
Detection difficulties
① Local discharge signals are weak and have short durations.
② Equipment structures are complex, and the discharge locations are concealed.
③ Traditional detection methods rely heavily on the experience of operators and are subject to strong interference.
Solution and detection method
Using the 72-channel acoustic imager for power equipment developed independently by wisono
Technology Co., Ltd. (model: AC-D100) and the 128-channel acoustic imager for power equipment (model: AC-D128PD),
a non-contact, long-distance, and visual acoustic source positioning method is adopted to capture characteristic
acoustic signals generated during local discharge.
Characteristics:
① Non-contact detection, applicable to energized equipment;
②It is not affected by electromagnetic interference, ensuring a safe and reliable detection process.
③ Can locate the discharge source from a certain distance away and determine the
type of partial discharge based on the sound pattern;
④ Real-time imaging, facilitating abnormal judgment and recording.
Explanation of the on-site detection process
① Determine the detection route based on the equipment layout in the substation;
② Scan key areas such as switch cabinets, busbar connections, insulators, transformers, and transmission cables;
③ Real-time observation of the acoustic imaging diagram, combined with the PRPD diagram,
capture the abnormal discharge sound source, and determine the type of partial discharge.
④ Reconfirm the suspected partial discharge points from multiple angles;
⑤ Record the acoustic images and detection data to form the basis of the detection.
Display of detection results and effects
Detection results: Can detect multiple suspected partial discharge sound sources in strong background noise
without stopping the equipment, through non-contact and long-distance detection.
Partial discharge locations: Transformer, transmission cables, inside the switch cabinet, insulator.

Figure 1-1 On-site measurement of partial discharge in the transmission cables of a certain substation in Guangzhou

Figure 1-2 On-site measurement of partial discharge in the transmission cables of a certain substation in Guangzhou

Figure 2-1 On-site measurement of Yunnan Power Grid (insulator discharge)

Figure 2-2 On-site measurement of Yunnan Power Grid (Electrical equipment discharge)

Figure 2-3 On-site measurement of Yunnan Power Grid (discharge inside switch cabinet)

Figure 2-4 On-site measurement of Yunnan Power Grid (discharge of transmission lines and cables)

Figure 3: Measured data of a 35kV transmission line in a certain area of Nanchang
Using an acoustic imaging instrument for detection, it was found that there was a local discharge problem (discharge type: tip discharge) at the rear insulator and compression ring
of a distribution substation fuse on the line. The fault point is approximately 15 meters above the ground. It is clearly identifiable that there is a discharge fault at this location and
the specific position can be distinguished. Currently, this point is being recorded and archived, and continuous tracking is being conducted.
It is planned to carry out equipment maintenance during the next planned power outage.

Figure 4: Actual measurement of a 10kV transmission line in a certain area of Guanyun County, Jiangsu Province
Using an acoustic imaging instrument for detection, it was found that there was a local discharge problem at a certain insulating ceramic terminal position of the line
(discharge type: surface discharge). The fault point is approximately 20 meters above the ground, with significant signal attenuation.
Traditional remote ultrasonic detection methods can only detect the presence of a discharge fault at this location but cannot determine the exact position.
Currently, this point is recorded and archived, and continuous tracking is being conducted. It is planned to carry out equipment maintenance during the next planned power outage.

Figure 5: Measured data of a 10kV transmission line for medium-voltage distribution in Foshan
Using an acoustic imaging instrument for inspection, it was discovered that there was a localized discharge problem
at the insulation position of the rear part of a drop-out fuse of a distribution substation on the line.
The fault point was approximately 5 meters above the ground. It was clearly identifiable that a discharge fault existed
at this location and the specific position could be distinguished. Currently, this point has been recorded and archived, and continuous tracking is being conducted.
It is planned to carry out equipment maintenance during the next planned power outage.

Figure 6 On-site measurement in Dongguan (Transformer discharge (Discharge type: Suspended discharge))

Figure 7 On-site measurement in Beijing (Insulator discharge (Discharge type: Tip discharge))
Customer feedback
① The customer recognized the practicality of acoustic imaging technology in the detection of partial discharges under live conditions.
② It helps to identify insulation defects in advance and prevent the expansion of equipment failures.
③ It is suitable for inclusion in the state maintenance and intelligent inspection system of substations.
④ It is of great significance for enhancing the safety of power grid operation.